WIT 28-55K-HU-AU-US L2
28 – 55 kWThree-phaseIP66
View details
MID 29.9-50K-HU
Hybrid inverter · Three-phase · 29.9 – 50 kW
29.9 – 50 kWThree-phaseIP66
Price on request
29.9 – 50 kWRated power
Three-phasePhase
3 – 4MPPT trackers
98.6 %Max. efficiency
Technical data
| MID 29.9K-HU | MID 30K-HU | MID 33K-HU | MID 36K-HU | MID 40K-HU | MID 50K-HU | |
|---|---|---|---|---|---|---|
| PV input | ||||||
| Max. PV input power (W) | 59800 | 60000 | 66000 | 72000 | 80000 | 100000 |
| Max. PV input voltage (V) | 1000 | |||||
| Rated PV input voltage (V) | 600 | |||||
| MPPT voltage range (V) | 200 – 1000 | |||||
| Full-power MPPT voltage range (V) | 400 – 800 | 400 – 800 | 400 – 800 | 400 – 800 | 450 – 800 | 450 – 800 |
| Start-up voltage (V) | 160 | |||||
| Max. input current per MPPT (A) | 40 | |||||
| Max. short-circuit current per MPPT (A) | 50 | |||||
| Number of MPPT trackers | 3 | 3 | 3 | 3 | 4 | 4 |
| PV strings per MPPT | 2 | |||||
| AC output | ||||||
| Rated output power (W) | 29900 | 30000 | 33000 | 36000 | 40000 | 50000 |
| Max. apparent power (VA) | 29900 | 33000 | 36300 | 39600 | 44000 | 50000 |
| Rated AC voltage (V) | 400 | |||||
| Rated AC voltage options (V) | 220/380; 230/400 | |||||
| Phase | Three-phase | |||||
| Grid connection type | 3W+N+PE / 3W+PE | |||||
| Rated AC frequency (Hz) | 50/60 | |||||
| Grid frequency range (50 Hz / 60 Hz) (Hz) | 45-55 / 55-65 | |||||
| Max. AC output current (A) | 45.3 | 50 | 55 | 60 | 66.7 | 75.8 |
| Power factor | > 0.99 at nominal power; adjustable 0.8 leading to 0.8 lagging | |||||
| Total harmonic distortion (THDi) (%) | <3 | |||||
| Three-phase unbalanced output | Supported only with APX HV Battery 1.0 / 2.0 | |||||
| AC nominal input power (grid side) (W) | 35900 | 36000 | 39600 | 43200 | 48000 | 60000 |
| Max. AC input apparent power (grid side) (VA) | 35900 | 36000 | 39600 | 43200 | 48000 | 60000 |
| Max. AC input current (grid side) (A) | 54.4 | 54.5 | 60 | 65.5 | 72.7 | 90.9 |
| Backup output power (W) | 29900 | 30000 | 33000 | 36000 | 40000 | 50000 |
| Max. backup apparent power (VA) | 29900 | 30000 | 33000 | 36000 | 40000 | 50000 |
| Nominal backup AC voltage (V) | 220/380; 230/400 | |||||
| Nominal backup AC frequency (Hz) | 50 / 60 | |||||
| Max. backup output current (A) | 45.3 | 45.5 | 50 | 54.5 | 60.6 | 75.8 |
| Peak (surge) power (W) | 35880 | 36000 | 39600 | 43200 | 48000 | 60000 |
| Backup overload duration (s) | 10 | |||||
| Backup THDv (%) | <3 | |||||
| Backup switch time (ms) | <150 | |||||
| Battery | ||||||
| Compatible battery | APX HV Battery 1.0; APX HV Battery 2.0 (5 kWh-30 kWh) | |||||
| Battery voltage range (V) | 600 – 980 | |||||
| Battery operating voltage range by battery model (V) | APX HV Battery 1.0: 600-980; APX HV Battery 2.0: 660-980 | |||||
| Max. battery operating current (APX HV Battery 1.0 / 2.0) (A) | 83.3 / 75.8 | |||||
| Max. discharge power with APX HV Battery 1.0 (W) | 29900 | 30000 | 30000 | 30000 | 30000 | 30000 |
| Max. discharge power with APX HV Battery 2.0 (W) | 29900 | 30000 | 33000 | 36000 | 40000 | 45000 |
| Max. charge power (W) | 50000 | |||||
| Efficiency | ||||||
| Max. efficiency (%) | 98.6 | |||||
| European efficiency (%) | 97.2 | |||||
| Protection | ||||||
| Protection functions | DC switch; DC reverse polarity protection; AC/DC surge protection (Type II); Insulation resistance monitoring; Output surge protection (Type II); AC short-circuit protection; Ground fault monitoring; Grid monitoring; Anti-islanding protection; Residual-current monitoring unit; String fault monitoring; AFCI protection (optional) | |||||
| General data | ||||||
| Dimensions (W x H x D) (mm) | 680 × 570 × 256 | |||||
| Weight (kg) | 48 | 48 | 48 | 48 | 50 | 50 |
| Operating temperature range (°C) | −25 – 60 | |||||
| Power derating above (°C) | 45 | |||||
| Noise level (dB) | ≤55 | |||||
| Max. operating altitude (m) | 4000 | |||||
| Night-time power consumption (W) | <25 | |||||
| Topology | Transformerless | |||||
| Cooling | Smart air cooling | |||||
| Ingress protection (IP rating) | IP66 | |||||
| Relative humidity (%) | 0 – 100 | |||||
| DC connection | H4 / MC4 (optional) | |||||
| AC connection | Waterproof PG connector + OT terminal | |||||
| Warranty (years) | 5 – 10 | |||||
| Communication | ||||||
| Display | OLED + LED / Wi-Fi + App | |||||
| Communication interfaces | RS485; CAN; USB | |||||
| Monitoring | Optional external monitoring modules (Wi-Fi/LAN, 4G, data logger) | |||||
| Certifications | ||||||
| Certifications and standards | CE | |||||
| Grid codes | N4105; EN 50549-1; C10/C11; CEI 0-21; G99; G100 | |||||
Values from the manufacturer's datasheet, pending final confirmation. The datasheet supplied with the product prevails.
Downloads
Applications
Works with
WIT 28-55K-HU-AU-US L2
28 – 55 kWThree-phaseIP66
View details
S6-EH3P(29.9-50)K-H
29.9 – 50 kWThree-phaseIP66
View details
S6-EH3P(29.9-60)K-H(21A)
29.9 – 60 kWThree-phaseIP66
View details
Request a quotation
You receive the datasheet, certificates, tiered pricing from your target quantity and a shipping date.