S6-EH3P(29.9-50)K-H
29.9 – 50 kWThree-phaseIP66
View details
S6-EH3P(29.9-60)K-H(21A)
Hybrid inverter · Three-phase · 29.9 – 60 kW
29.9 – 60 kWThree-phaseIP66
Price on request
29.9 – 60 kWRated power
Three-phasePhase
3 – 4MPPT trackers
97.7 %Max. efficiency
Technical data
| S6-EH3P29.9K-H(21A) | S6-EH3P30K-H(21A) | S6-EH3P40K-H(21A) | S6-EH3P49K-H(21A) | S6-EH3P50K-H(21A) | S6-EH3P60K-H(21A) | |
|---|---|---|---|---|---|---|
| PV input | ||||||
| Max. PV input power (W) | 59800 | 60000 | 80000 | 98000 | 100000 | 100000 |
| Max. usable PV input power (W) | 59800 | 60000 | 80000 | 98000 | 100000 | 100000 |
| Max. PV input voltage (V) | 1000 | |||||
| Rated PV input voltage (V) | 600 | |||||
| Start-up voltage (V) | 180 | |||||
| MPPT voltage range (V) | 150 – 850 | |||||
| Max. input current per MPPT (A) | 42 | |||||
| Max. short-circuit current per MPPT (A) | 60 | |||||
| Number of MPPT trackers | 3 | 3 | 4 | 4 | 4 | 4 |
| Max. number of PV input strings | 6 | 6 | 8 | 8 | 8 | 8 |
| Max. string input current (A) | 21 | |||||
| AC output | ||||||
| Rated output power (W) | 29900 | 30000 | 40000 | 49000 | 50000 | 60000 |
| Max. apparent power (VA) | 29900 | 30000 | 40000 | 49000 | 50000 | 60000 |
| Rated AC voltage (V) | 400 | |||||
| Rated grid voltage options (V) | 220/380; 230/400 | |||||
| Rated AC output current (A) | 43.2 | 43.3 | 57.7 | 70.7 | 72.2 | 86.6 |
| Phase | Three-phase | |||||
| Rated AC frequency (Hz) | 50/60 | |||||
| Power factor | > 0.99 (0.8 leading to 0.8 lagging) | |||||
| Total harmonic distortion (THDi) (%) | <3 | |||||
| Max. grid input power (W) | 59800 | 60000 | 80000 | 98000 | 100000 | 100000 / 105000 |
| Grid input voltage range (V) | 304 – 460 | |||||
| Max. grid input current (380 V / 400 V) (A) | 90.8 / 86.4 | 91.2 / 86.6 | 121.6 / 115.4 | 149 / 141.4 | 152 / 144.4 | 152 / 152 |
| Backup output power (W) | 29900 | 30000 | 40000 | 49000 | 50000 | 60000 |
| Peak (surge) power (W) | 59800 | 60000 | 80000 | 98000 | 100000 | 120000 |
| Overload capability, critical-load output | 2 x rated power for 1.6 s; 1.5 x rated power for 10 s | |||||
| Grid / off-grid switchover time (ms) | <10 | |||||
| Rated output voltage, critical-load output (V) | 380 / 400 | |||||
| Rated output frequency, critical-load output (Hz) | 50 / 60 | |||||
| Rated output current, critical-load output (380 V / 400 V) (A) | 45.4 / 43.2 | 45.6 / 43.3 | 60.8 / 57.7 | 74.5 / 70.7 | 76 / 72.2 | 91.2 / 86.6 |
| Max. bypass current, critical-load output (380 V / 400 V) (A) | 45.4 / 43.2 | 45.6 / 43.3 | 60.8 / 57.7 | 74.5 / 70.7 | 76 / 72.2 | 91.2 / 86.6 |
| Total voltage harmonic distortion (THDv), critical-load output (%) | <2 | |||||
| Generator input | Yes | |||||
| Max. generator input power (W) | 29900 | 30000 | 40000 | 49000 | 50000 | 60000 |
| Generator rated input current (380 V / 400 V) (A) | 45.4 / 43.2 | 45.6 / 43.3 | 60.8 / 57.7 | 74.5 / 70.7 | 76 / 72.2 | 91.2 / 86.6 |
| Max. system capacity with parallel units (kW) | 600 | |||||
| Battery | ||||||
| Battery type | Lithium battery | |||||
| Battery voltage range (V) | 150 – 800 | |||||
| Max. charge current (A) | 160 | 160 | 160 | 160 | 160 | 168 |
| Max. discharge current (A) | 160 | 160 | 160 | 160 | 160 | 168 |
| Number of battery inputs / BMS ports | 2 | |||||
| Max. charge / discharge current per battery input (A) | 80 | 80 | 80 | 80 | 80 | 84 |
| Compatible battery module capacity (Ah) | 100 – 314 | |||||
| Battery communication | CAN | |||||
| Efficiency | ||||||
| Max. efficiency (%) | 97.7 | |||||
| European efficiency (%) | 97.3 | |||||
| Battery charging efficiency (%) | 98.5 / 97.8 | |||||
| Battery discharging efficiency (%) | 97.5 | |||||
| Protection | ||||||
| Protection functions | Surge protection (DC Type II / AC Type II); AC output overcurrent protection; Insulation resistance protection; Residual current (RCD) detection; Integrated PV switch; DC reverse polarity protection; DC arc fault protection (optional); Anti-islanding protection | |||||
| Protection class / overvoltage category | Class I / PV II, battery II, AC III | |||||
| General data | ||||||
| Dimensions (W x H x D) (mm) | 530 × 880 × 290 | |||||
| Weight (kg) | 76 | |||||
| Topology | Non-isolated | |||||
| Operating temperature range (°C) | −25 – 60 | |||||
| Relative humidity (%) | 0 – 100 | |||||
| Ingress protection (IP rating) | IP66 | |||||
| Cooling | Intelligent redundant air cooling | |||||
| Max. operating altitude (m) | 4000 | |||||
| Night-time power consumption (W) | <35 | |||||
| Max. single-phase load capacity | 33% of rated power | |||||
| PV connector | MC4 quick-plug terminal | |||||
| Battery connector | Terminal block | |||||
| AC connector | OT terminal | |||||
| Communication | ||||||
| Display | 7-inch LCD, Bluetooth + app | |||||
| Communication interfaces | Wi-Fi; LAN; Bluetooth; CAN-BMS x2; CAN-Parallel x2; RS485-Meter; RS485; DRM; DI x3; DO x3; 4G (optional) | |||||
| Certifications | ||||||
| Certifications and standards | IEC/EN 62109-1/-2; IEC/EN 61000-6-2/-4; EN 55011 | |||||
| Grid codes | Planned: G99; VDE-AR-N 4105/VDE V 0124; EN 50549-1/EN 50549-10; PTPiREE; VDE 0126/XP C15/VFR:2019; NTS 631/RD 1699/UNE 217002; CEI 0-21; CEI 0-16; C10/11; NRS 097-2-1; TOR; EIFS 2018.2; IEC 62116; IEC 61727; DEWA; MEA; PEA; PORTARIA Nº 140/PORTARIA Nº 515 | |||||
Values from the manufacturer's datasheet, pending final confirmation. The datasheet supplied with the product prevails.
Downloads
Applications
Works with
S6-EH3P(29.9-50)K-H
29.9 – 50 kWThree-phaseIP66
View details
SUN-29.9-50K-SG01HP3-EU-BM3-BM4
29.9 – 50 kWThree-phaseIP65
View details
SUN-29.9-50K-SG02HP3-EU-BM3-BM4-P
29.9 – 50 kWThree-phaseIP65
View details
Request a quotation
You receive the datasheet, certificates, tiered pricing from your target quantity and a shipping date.