S6-EH3P(15-20)K-H Hybrid inverter

S6-EH3P(15-20)K-H

Hybrid inverter · Three-phase · 15 – 20 kW

15 – 20 kWThree-phaseIP66
Price on request
15 – 20 kWRated power
Three-phasePhase
4MPPT trackers
97.7 %Max. efficiency

Technical data

S6-EH3P15K-HS6-EH3P20K-H
PV input
Max. PV input power (W)3000040000
Max. usable PV input power (W)2400032000
Max. PV input voltage (V)1000
Rated PV input voltage (V)600
MPPT voltage range (V)200 – 850
Start-up voltage (V)160
Max. input current per MPPT (A)20
Max. input current per string (A)20
Max. short-circuit current per MPPT (A)30
Number of MPPT trackers4
Max. number of PV input strings4
AC output
Rated output power (W)1500020000
Max. apparent power (VA)1500020000
Rated AC voltage (V)400
Rated AC output current (A)21.728.9
PhaseThree-phase
Rated AC frequency (Hz)50/60
Power factor>0.99 (0.8 leading to 0.8 lagging)
Total harmonic distortion (THDi) (%)<3
Max. AC input power (grid side) (W)2250030000
AC input voltage range (grid side, 380 V / 400 V) (V)304-437 / 320-460
Max. AC input current (grid side, 380 V / 400 V) (A)34.2 / 32.545.6 / 43.3
Backup output power (W)1500020000
Peak (surge) power (W)2400032000
Off-grid overload duration (s)10
Grid / off-grid switchover time, single unit (ms)<10
Grid / off-grid switchover time, parallel system (up to 6 units) (ms)<20
Rated output voltage, off-grid side3/N/PE, 220 V / 380 V, 230 V / 400 V
Rated frequency, off-grid side (Hz)50 / 60
Rated output current, off-grid side (380 V / 400 V) (A)22.8 / 21.730.4 / 28.9
Max. bypass current (380 V / 400 V) (A)34.2 / 32.545.6 / 43.3
Total voltage harmonic distortion (THDv), off-grid side (%)<3
Generator inputYes
Max. input power, generator side (W)1500020000
Rated input current, generator side (380 V / 400 V) (A)22.8 / 21.730.4 / 28.9
Rated input voltage, generator side3/N/PE, 220 V / 380 V, 230 V / 400 V
Rated input frequency, generator side (Hz)50 / 60
Battery
Battery typeLithium battery
Battery voltage range (V)120 – 800
Max. charge current (A)50
Max. discharge current (A)50
Number of battery ports / BMS ports1 / 1
Battery communicationCAN / RS485
Efficiency
Max. efficiency (%)97.7
European efficiency (%)97.5
Battery charging efficiency (%)98.5 / 97.2
Battery discharging efficiency (%)97.2
Protection
Protection functionsSurge protection (DC Type II / AC Type II optional); AC output overcurrent protection; Insulation resistance protection; Residual current (RCD) detection; Integrated PV switch; DC reverse polarity protection; Anti-islanding protection
Protection class / overvoltage categoryClass I / OVC II (PV and battery ports), OVC III (grid, off-grid and generator ports)
General data
Dimensions (W x H x D) (mm)563 × 546 × 250
Weight (kg)35.2
TopologyTransformerless
Night-time power consumption (W)<25
Operating temperature range (°C)−25 – 60
Relative humidity (%)0 – 100
Ingress protection (IP rating)IP66
Noise level (dB)<65
CoolingIntelligent redundant air cooling
Max. operating altitude (m)2000
Max. single-phase load capacity40% of rated power
PV connectorMC4 quick-connect plug
Battery connectorCrimp terminal
AC connectorOT terminal
Communication
Display7-inch LCD, Bluetooth + app
Communication interfacesWi-Fi; LAN; Bluetooth; CAN-BMS; CAN-Parallel x 2; RS485-Meter; RS485; DRM; DI; DO x 3
Certifications
Certifications and standardsIEC/EN 62109-1/-2; IEC/EN 61000-6-1/-2/-3/-4
Grid codesEN 50549-1/-10; VDE 4105; CEI 0-21; CEI 0-16; NC-RFG Type B; NRS 097-2-1; LTU-1; G99; PEA

Values from the manufacturer's datasheet, pending final confirmation. The datasheet supplied with the product prevails.

Downloads

Datasheets

Applications

Works with

Request a quotation

You receive the datasheet, certificates, tiered pricing from your target quantity and a shipping date.

Fields marked * are required.

One working day reply. Your details are used for this quote only. How we handle your data: Privacy

Price on request Get a quote