MAX 100-150KTL3-X2 LV-MV
100 – 150 kWThree-phaseIP66
View details
SUN-120-136K-G01P3-EU-AM8
String inverter · Three-phase · 120 – 136 kW
120 – 136 kWThree-phaseIP65
Price on request
120 – 136 kWRated power
Three-phasePhase
8MPPT trackers
98.8 %Max. efficiency
Technical data
| SUN-120K-G01P3-EU-AM8 | SUN-125K-G01P3-EU-AM8 | SUN-130K-G01P3-EU-AM8 | SUN-135K-G01P3-EU-AM8 | SUN-136K-G01P3-EU-AM8 | |
|---|---|---|---|---|---|
| PV input | |||||
| Max. PV input power (W) | 180000 | 187500 | 195000 | 202500 | 204000 |
| Max. PV input voltage (V) | 1100 | ||||
| Rated PV input voltage (V) | 600 | ||||
| MPPT voltage range (V) | 200 – 1000 | ||||
| Start-up voltage (V) | 250 | ||||
| Max. input current per MPPT (A) | 40 | ||||
| Max. short-circuit current per MPPT (A) | 60 | ||||
| Number of MPPT trackers | 8 | ||||
| PV strings per MPPT | 4 | ||||
| AC output | |||||
| Rated output power (W) | 120000 | 125000 | 130000 | 135000 | 136000 |
| Max. apparent power (VA) | 132000 | 135000 | 135000 | 135000 | 136000 |
| Rated AC voltage (V) | 400 | ||||
| Rated AC voltage options and range | 220/380 V; 230/400 V; range 0.85 Un-1.1 Un | ||||
| Rated AC output current (A) | 174 | 181.2 | 188.5 | 195.7 | 197.2 |
| Max. AC output current (A) | 191.4 | 195.7 | 195.7 | 195.7 | 197.2 |
| Phase | Three-phase | ||||
| Grid connection type | 3L/N/PE | ||||
| Rated AC frequency (Hz) | 50/60 | ||||
| Rated AC frequency and range | 50 Hz (45-55 Hz); 60 Hz (55-65 Hz) | ||||
| Power factor | 0.8 leading to 0.8 lagging | ||||
| Total harmonic distortion (THDi) (%) | <3 | ||||
| DC injection current | <0.5% In | ||||
| Efficiency | |||||
| Max. efficiency (%) | 98.8 | ||||
| European efficiency (%) | 98.2 | ||||
| MPPT efficiency (%) | >99 | ||||
| Protection | |||||
| Protection functions | DC reverse polarity protection; AC output overcurrent protection; AC output overvoltage protection; AC output short circuit protection; Thermal protection; Insulation impedance detection; DC component monitoring; Arc fault circuit interrupter (AFCI) (optional); Anti-PID function (optional); Anti-islanding protection; Residual current detection; Type II DC surge protection; Type II AC surge protection; DC switch | ||||
| General data | |||||
| Dimensions (W x H x D) (mm) | 1006 × 516 × 325.5 | ||||
| Weight (kg) | 103 | ||||
| Ingress protection (IP rating) | IP65 | ||||
| Operating temperature range (°C) | −25 – 60 | ||||
| Power derating starts above (°C) | 45 | ||||
| Relative humidity (%) | 0 – 100 | ||||
| Max. operating altitude (m) | 4000 | ||||
| Noise level (dB) | ≤65 | ||||
| Cooling | Intelligent air cooling | ||||
| Topology | Non-isolated | ||||
| Overvoltage category | OVC II (DC), OVC III (AC) | ||||
| Warranty (years) | 5 | ||||
| Communication | |||||
| Communication interfaces | RS485; RS232 | ||||
| Monitoring | GPRS / Wi-Fi / Bluetooth / 4G / LAN (optional) | ||||
| Certifications | |||||
| Certifications and standards | IEC/EN 61000-6-1/2/3/4; IEC/EN 62109-1; IEC/EN 62109-2 | ||||
| Grid codes | IEC 61727; IEC 62116; CEI 0-21; EN 50549; NRS 097; RD 140; UNE 217002; OVE-Richtlinie R25; G99; VDE-AR-N 4105 | ||||
Values from the manufacturer's datasheet, pending final confirmation. The datasheet supplied with the product prevails.
Downloads
Applications