MAX 100-150KTL3-X LV
100 – 150 kWThree-phaseIP66
View details
MAX 100-150KTL3-X2 LV-MV
String inverter · Three-phase · 100 – 150 kW
100 – 150 kWThree-phaseIP66
Price on request
100 – 150 kWRated power
Three-phasePhase
8MPPT trackers
98.8 – 99 %Max. efficiency
Technical data
| MAX 100KTL3-X2 LV | MAX 110KTL3-X2 LV | MAX 120KTL3-X2 LV | MAX 124KTL3-X2 MV | MAX 125KTL3-X2 LV | MAX 125KTL3-X2 MV | MAX 136KTL3-X2 MV | MAX 150KTL3-X2 MV | |
|---|---|---|---|---|---|---|---|---|
| PV input | ||||||||
| Max. PV input power (W) | 150000 | 165000 | 180000 | 186000 | 187500 | 187500 | 204000 | 204000 |
| Max. PV input voltage (V) | 1100 | |||||||
| Rated PV input voltage (V) | 600 | 600 | 600 | 720 | 600 | 720 | 720 | 720 |
| MPPT voltage range (V) | 180 – 1000 | |||||||
| Start-up voltage (V) | 195 | |||||||
| Max. input current per MPPT (A) | 45 | |||||||
| Max. short-circuit current per MPPT (A) | 56.5 | |||||||
| Number of MPPT trackers | 8 | |||||||
| PV strings per MPPT | 2 | |||||||
| AC output | ||||||||
| Rated output power (W) | 100000 | 110000 | 120000 | 124000 | 125000 | 125000 | 136000 | 150000 |
| Max. apparent power (VA) | 110000 | 121000 | 132000 | 136400 | 137500 | 137500 | 150000 | 165000 |
| Rated AC voltage (V) | 400 | 400 | 400 | 480 | 400 | 480 | 480 | 480 |
| Nominal AC voltage options and range | 220/380 V; 230/400 V (340-440 V) | 220/380 V; 230/400 V (340-440 V) | 220/380 V; 230/400 V (340-440 V) | 277/480 V (408-528 V) | 220/380 V; 230/400 V (340-440 V) | 277/480 V (408-528 V) | 277/480 V (408-528 V) | 277/480 V (408-528 V) |
| Phase | Three-phase | |||||||
| AC grid connection type | 3W/N/PE | 3W/N/PE | 3W/N/PE | 3W/PE | 3W/N/PE | 3W/PE | 3W/PE | 3W/PE |
| Rated AC frequency (Hz) | 50/60 | |||||||
| Rated AC frequency and range | 50/60 Hz (45-55 Hz / 55-65 Hz) | |||||||
| Max. AC output current (A) | 158.8 | 174.6 | 190.5 | 164.1 | 198.5 | 165.4 | 179.9 | 198.5 |
| Max. output current at 380 V (A) | 167.1 | 183.8 | 200.5 | – | 208.9 | – | – | – |
| Power factor | 0.8 leading to 0.8 lagging (adjustable) | |||||||
| Total harmonic distortion (THDi) (%) | <3 | |||||||
| Efficiency | ||||||||
| Max. efficiency (%) | 98.8 | 98.8 | 98.8 | 99 | 98.8 | 99 | 99 | 99 |
| European efficiency (%) | 98.4 | 98.5 | 98.5 | 98.5 | 98.5 | 98.5 | 98.5 | 98.5 |
| MPPT efficiency (%) | 99.9 | |||||||
| Protection | ||||||||
| Protection functions | DC reverse polarity protection; DC switch; Type II DC surge protection; Type II AC surge protection; Insulation resistance monitoring; AC short-circuit protection; Ground fault monitoring; String detection; Anti-PID function (optional); Arc fault detection (AFCI) (optional) | |||||||
| General data | ||||||||
| Dimensions (W x H x D) (mm) | 970 × 640 × 345 | |||||||
| Weight (kg) | 84 | |||||||
| Ingress protection (IP rating) | IP66 | |||||||
| Corrosion protection class | – | – | – | C5 | – | C5 | C5 | C5 |
| Operating temperature range (°C) | −30 – 60 | |||||||
| Relative humidity (%) | 0 – 100 | |||||||
| Max. operating altitude (m) | 4000 | |||||||
| Cooling | Smart air cooling | |||||||
| Topology | Transformerless | |||||||
| Night-time power consumption (W) | <1 | |||||||
| Warranty (years) | 5 – 10 | |||||||
| DC connection | H4 / MC4 (optional) | |||||||
| AC connection | Cable gland + OT terminal | |||||||
| Communication | ||||||||
| Display | LED / Wi-Fi + app | |||||||
| Communication interfaces | RS485; USB; GPRS (optional); 4G (optional); Wi-Fi (optional) | |||||||
| Certifications | ||||||||
| Certifications and standards | CE; UKCA; CB; BIS; IEC 61683; IEC 60068 | CE; UKCA; CB; BIS; IEC 61683; IEC 60068 | CE; UKCA; CB; BIS; IEC 61683; IEC 60068 | CE | CE; UKCA; CB; BIS; IEC 61683; IEC 60068 | CE | CE | CE |
| Grid codes | IEC 62116; IEC 61727; Poland Type A/B; CEI 0-16; CEI 0-21; C10/C11; EN 50549-1; EN 50549-2; EN 50549-1/10; VDE-AR-N 4105; VDE-AR-N 4110; VDE 0126; UNE 217001; UNE 217002; NTS Type C; IEEE 1547; UL 1741 | IEC 62116; IEC 61727; Poland Type A/B; CEI 0-16; CEI 0-21; C10/C11; EN 50549-1; EN 50549-2; EN 50549-1/10; VDE-AR-N 4105; VDE-AR-N 4110; VDE 0126; UNE 217001; UNE 217002; NTS Type C; IEEE 1547; UL 1741 | IEC 62116; IEC 61727; Poland Type A/B; CEI 0-16; CEI 0-21; C10/C11; EN 50549-1; EN 50549-2; EN 50549-1/10; VDE-AR-N 4105; VDE-AR-N 4110; VDE 0126; UNE 217001; UNE 217002; NTS Type C; IEEE 1547; UL 1741 | IEC 62116; IEC 61727; UL 1741; IEEE 1547 | IEC 62116; IEC 61727; Poland Type A/B; CEI 0-16; CEI 0-21; C10/C11; EN 50549-1; EN 50549-2; EN 50549-1/10; VDE-AR-N 4105; VDE-AR-N 4110; VDE 0126; UNE 217001; UNE 217002; NTS Type C; IEEE 1547; UL 1741 | IEC 62116; IEC 61727; UL 1741; IEEE 1547 | IEC 62116; IEC 61727; UL 1741; IEEE 1547 | IEC 62116; IEC 61727; UL 1741; IEEE 1547 |
Values from the manufacturer's datasheet, pending final confirmation. The datasheet supplied with the product prevails.
Downloads
Applications