G6-GC3P40K-NV-ND
40 kWThree-phaseIP66
View details
SUN-40-50K-G04
String inverter · Three-phase · 40 – 50 kW
40 – 50 kWThree-phaseIP65
Price on request
40 – 50 kWRated power
Three-phasePhase
3 – 4MPPT trackers
98.7 %Max. efficiency
Technical data
| SUN-40K-G04 | SUN-45K-G04 | SUN-50K-G04 | |
|---|---|---|---|
| PV input | |||
| Max. PV input power (W) | 52000 | 58500 | 65000 |
| Max. PV input voltage (V) | 1100 | ||
| Rated PV input voltage (V) | 600 | ||
| MPPT voltage range (V) | 200 – 1000 | ||
| Start-up voltage (V) | 250 | ||
| Max. input current per MPPT (A) | 40 | ||
| Max. short-circuit current per MPPT (A) | 60 | ||
| Number of MPPT trackers | 3 | 3 | 4 |
| PV strings per MPPT | 3 | ||
| AC output | |||
| Rated output power (W) | 40000 | 45000 | 50000 |
| Max. apparent power (VA) | 44000 | 49500 | 55000 |
| Rated AC voltage (V) | 400 | ||
| Rated AC voltage options (V) | 220/380; 230/400 | ||
| AC voltage range (relative to rated voltage) | 0.85 Un-1.1 Un | ||
| Rated AC output current (A) | 58 | 65.2 | 72.5 |
| Max. AC output current (A) | 63.8 | 71.7 | 79.7 |
| Phase | Three-phase | ||
| Grid connection type | 3L/N/PE | ||
| Rated AC frequency (Hz) | 50/60 | ||
| Grid frequency range (50 Hz / 60 Hz) (Hz) | 45-55 / 55-65 | ||
| Power factor | 0.8 leading to 0.8 lagging | ||
| Total harmonic distortion (THDi) (%) | <3 | ||
| DC injection current | <0.5% In | ||
| Efficiency | |||
| Max. efficiency (%) | 98.7 | ||
| European efficiency (%) | 98.1 | ||
| MPPT efficiency (%) | >99 | ||
| Protection | |||
| Protection functions | DC reverse polarity protection; AC output overcurrent protection; AC output overvoltage protection; AC output short-circuit protection; Thermal protection; Insulation impedance detection; DC component monitoring; Arc fault circuit interrupter (AFCI) (optional); Anti-islanding protection; Residual current detection; DC switch | ||
| Surge protection level | Type II (DC), Type II (AC) | ||
| Anti-PID function | Optional | ||
| General data | |||
| Dimensions (W x H x D) (mm) | 434 × 570 × 243 | ||
| Weight (kg) | 39 | ||
| Ingress protection (IP rating) | IP65 | ||
| Operating temperature range (°C) | −25 – 60 | ||
| Power derating above (°C) | 45 | ||
| Relative humidity (%) | 0 – 100 | ||
| Max. operating altitude (m) | 4000 | ||
| Cooling | Intelligent air cooling | ||
| Noise level (dB) | <65 | ||
| Topology | Non-isolated | ||
| Overvoltage category | OVC II (DC), OVC III (AC) | ||
| Warranty (years) | 5 | ||
| Communication | |||
| Communication interfaces | RS485; RS232 | ||
| Monitoring | GPRS / Wi-Fi / Bluetooth / 4G / LAN (optional); string intelligent monitoring (optional) | ||
| Certifications | |||
| Certifications and standards | IEC/EN 61000-6-1/2/3/4; IEC/EN 62109-1; IEC/EN 62109-2 | ||
| Grid codes | IEC 61727; IEC 62116; CEI 0-21; EN 50549; NRS 097; RD 140; UNE 217002; OVE-Richtlinie R25; G99; VDE-AR-N 4105 | ||
Values from the manufacturer's datasheet, pending final confirmation. The datasheet supplied with the product prevails.
Downloads
Applications
Works with
G6-GC3P40K-NV-ND
40 kWThree-phaseIP66
View details
G6-GC(50-60)K-PRO
50 – 60 kWThree-phaseIP66
View details
MAC 50-70KTL3-X LV-MV
50 – 70 kWThree-phaseIP65
View details
Request a quotation
You receive the datasheet, certificates, tiered pricing from your target quantity and a shipping date.