MAX 100-150KTL3-X LV String inverter

MAX 100-150KTL3-X LV

String inverter · Three-phase · 100 – 150 kW

100 – 150 kWThree-phaseIP66
Price on request
100 – 150 kWRated power
Three-phasePhase
10MPPT trackers
98.8 %Max. efficiency

Technical data

MAX 100KTL3-X LVMAX 110KTL3-X LVMAX 120KTL3-X LVMAX 125KTL3-X LVMAX 150KTL3-X LV
PV input
Max. PV input power (W)150000165000180000187500225000
Max. PV input voltage (V)1100
Rated PV input voltage (V)600
MPPT voltage range (V)180 – 1000
Start-up voltage (V)195
Max. input current per MPPT (A)3232323245
Max. short-circuit current per MPPT (A)4040404056.5
Number of MPPT trackers10
PV strings per MPPT22223
AC output
Rated output power (W)100000110000120000125000150000
Max. apparent power (VA)110000121000132000137500165000
Rated AC voltage (V)400
Nominal AC voltage options and range220/380 V; 230/400 V (340-440 V)
PhaseThree-phase
AC grid connection type3W/N/PE
Rated AC frequency (Hz)50/60
Rated AC frequency and range50/60 Hz (45-55 Hz / 55-65 Hz)
Max. AC output current (A)158.8174.6190.5198.5238.2
Max. output current at 380 V (A)167.1183.8200.5208.9250.7
Power factor0.8 leading to 0.8 lagging (adjustable)
Total harmonic distortion (THDi) (%)<3
Efficiency
Max. efficiency (%)98.8
European efficiency (%)98.498.598.598.598.4
MPPT efficiency (%)99.9
Protection
Protection functionsDC reverse polarity protection; DC switch; Type II DC surge protection; Type II AC surge protection; Insulation resistance monitoring; AC short-circuit protection; Ground fault monitoring; String detection; Anti-PID function; Arc fault detection (AFCI)DC reverse polarity protection; DC switch; Type II DC surge protection; Type II AC surge protection; Insulation resistance monitoring; AC short-circuit protection; Ground fault monitoring; String detection; Anti-PID function; Arc fault detection (AFCI)DC reverse polarity protection; DC switch; Type II DC surge protection; Type II AC surge protection; Insulation resistance monitoring; AC short-circuit protection; Ground fault monitoring; String detection; Anti-PID function; Arc fault detection (AFCI)DC reverse polarity protection; DC switch; Type II DC surge protection; Type II AC surge protection; Insulation resistance monitoring; AC short-circuit protection; Ground fault monitoring; String detection; Anti-PID function; Arc fault detection (AFCI)DC reverse polarity protection; DC switch; Type II DC surge protection; Type II AC surge protection; Insulation resistance monitoring; AC short-circuit protection; Ground fault monitoring; String detection; Anti-PID function (optional); Arc fault detection (AFCI) (optional)
General data
Dimensions (W x H x D) (mm)970 × 640 × 345970 × 640 × 345970 × 640 × 345970 × 640 × 3451075 × 640 × 367
Weight (kg)8484848493
Ingress protection (IP rating)IP66
Operating temperature range (°C)−30 – 60
Relative humidity (%)0 – 100
Max. operating altitude (m)4000
CoolingSmart air cooling
TopologyTransformerless
Night-time power consumption (W)<1
Warranty (years)5 – 10
DC connectionH4 / MC4 (max. 6 mm²)
AC connectionOT terminal (max. 240 mm²)
Communication
DisplayLED / Wi-Fi + app
Communication interfacesRS485; USB; PLC (optional); GPRS (optional); 4G (optional)RS485; USB; PLC (optional); GPRS (optional); 4G (optional)RS485; USB; PLC (optional); GPRS (optional); 4G (optional)RS485; USB; PLC (optional); GPRS (optional); 4G (optional)RS485; USB; PLC (optional); GPRS (optional); 4G (optional); Wi-Fi (optional)
Certifications
Certifications and standardsCE; UKCA; CB; BIS; IEC 61683; IEC 60068CE; UKCA; CB; BIS; IEC 61683; IEC 60068CE; UKCA; CB; BIS; IEC 61683; IEC 60068CE; UKCA; CB; BIS; IEC 61683; IEC 60068CE
Grid codesIEC 62116; IEC 61727; Poland Type A/B; CEI 0-16; CEI 0-21; C10/C11; EN 50549-1; EN 50549-2; EN 50549-1/10; VDE-AR-N 4105; VDE-AR-N 4110; VDE 0126; UNE 217001; UNE 217002; NTS Type C; IEEE 1547; UL 1741IEC 62116; IEC 61727; Poland Type A/B; CEI 0-16; CEI 0-21; C10/C11; EN 50549-1; EN 50549-2; EN 50549-1/10; VDE-AR-N 4105; VDE-AR-N 4110; VDE 0126; UNE 217001; UNE 217002; NTS Type C; IEEE 1547; UL 1741IEC 62116; IEC 61727; Poland Type A/B; CEI 0-16; CEI 0-21; C10/C11; EN 50549-1; EN 50549-2; EN 50549-1/10; VDE-AR-N 4105; VDE-AR-N 4110; VDE 0126; UNE 217001; UNE 217002; NTS Type C; IEEE 1547; UL 1741IEC 62116; IEC 61727; Poland Type A/B; CEI 0-16; CEI 0-21; C10/C11; EN 50549-1; EN 50549-2; EN 50549-1/10; VDE-AR-N 4105; VDE-AR-N 4110; VDE 0126; UNE 217001; UNE 217002; NTS Type C; IEEE 1547; UL 1741IEC 62116; IEC 61727

Values from the manufacturer's datasheet, pending final confirmation. The datasheet supplied with the product prevails.

Downloads

Datasheets

User manuals

  • MAX 100-150KTL3-X LV user manual (English)PDF · 3.8 MBDownload

Applications

Works with

Request a quotation

You receive the datasheet, certificates, tiered pricing from your target quantity and a shipping date.

Fields marked * are required.

One working day reply. Your details are used for this quote only. How we handle your data: Privacy

Price on request Get a quote