MAX 50-80KTL3 LV
50 – 80 kWThree-phaseIP65
View details
SUN-60-75K-G01P3-EU-AM8-LV
String inverter · Three-phase · 60 – 75 kW
60 – 75 kWThree-phaseIP65
Price on request
60 – 75 kWRated power
Three-phasePhase
8MPPT trackers
98.7 %Max. efficiency
Technical data
| SUN-60K-G01P3-EU-AM8-LV | SUN-70K-G01P3-EU-AM8-LV | SUN-75K-G01P3-EU-AM8-LV | |
|---|---|---|---|
| PV input | |||
| Max. PV input power (W) | 90000 | 105000 | 112500 |
| Max. PV input voltage (V) | 800 | ||
| Start-up voltage (V) | 250 | ||
| MPPT voltage range (V) | 200 – 700 | ||
| Rated PV input voltage (V) | 500 | ||
| Max. input current per MPPT (A) | 40 | ||
| Max. short-circuit current per MPPT (A) | 60 | ||
| Number of MPPT trackers | 8 | ||
| PV strings per MPPT | 4 | ||
| AC output | |||
| Rated output power (W) | 60000 | 70000 | 75000 |
| Max. apparent power (VA) | 60000 | 70000 | 75000 |
| Rated AC voltage (V) | 230 | ||
| Rated AC voltage options (phase / line) (V) | 127/220; 133/230 | ||
| AC voltage range | 0.85 Un-1.1 Un | ||
| Phase | Three-phase | ||
| Grid connection form | 3L / N / PE | ||
| Rated AC output current (A) | 150.4 | 175.5 | 188 |
| Rated AC output current at 220 V line voltage (A) | 157.5 | 183.8 | 196.9 |
| Max. AC output current (A) | 150.4 | 175.5 | 188 |
| Max. AC output current at 220 V line voltage (A) | 157.5 | 183.8 | 196.9 |
| Rated AC frequency (Hz) | 50/60 | ||
| AC grid frequency range (50 Hz / 60 Hz) (Hz) | 45-55 / 55-65 | ||
| Power factor | 0.8 leading to 0.8 lagging (adjustable) | ||
| Total harmonic distortion (THDi) (%) | <3 | ||
| DC injection current | <0.5% In | ||
| Efficiency | |||
| Max. efficiency (%) | 98.7 | ||
| MPPT efficiency (%) | >99 | ||
| Protection | |||
| Protection functions | DC reverse polarity protection; AC output overcurrent protection; AC output overvoltage protection; AC output short-circuit protection; Thermal protection; Insulation impedance detection; DC component monitoring; Arc fault circuit interrupter (AFCI) (optional); Anti-islanding protection; Residual current detection; DC switch | ||
| Surge protection level | Type II (DC), Type II (AC) | ||
| Anti-PID function | Optional | ||
| General data | |||
| Dimensions (W x H x D) (mm) | 1006 × 516 × 325.5 | ||
| Weight (kg) | 103 | ||
| Ingress protection (IP rating) | IP65 | ||
| Operating temperature range (°C) | −25 – 60 | ||
| Power derating above (°C) | 45 | ||
| Relative humidity (%) | 0 – 100 | ||
| Max. operating altitude (m) | 4000 | ||
| Noise level (dB) | ≤55 | ||
| Cooling | Intelligent air cooling | ||
| Topology | Non-isolated | ||
| Overvoltage category | OVC II (DC), OVC III (AC) | ||
| Warranty (years) | 5 | ||
| Communication | |||
| Communication interfaces | RS485; RS232 | ||
| Monitoring | GPRS / Wi-Fi / Bluetooth / 4G / LAN (optional) | ||
| String intelligent monitoring | Optional | ||
| Certifications | |||
| Certifications and standards | IEC/EN 61000-6-1/2/3/4; IEC/EN 62109-1; IEC/EN 62109-2 | ||
| Grid codes | NBR 16149; NBR 16150; EN 50549; RD 140 | ||
Values from the manufacturer's datasheet, pending final confirmation. The datasheet supplied with the product prevails.
Downloads
Applications
Works with
MAX 50-80KTL3 LV
50 – 80 kWThree-phaseIP65
View details
SUN-60-80K-G04P3-EU-AM4
60 – 80 kWThree-phaseIP65
View details
SUN-70-110K-G03
70 – 110 kWThree-phaseIP65
View details
Request a quotation
You receive the datasheet, certificates, tiered pricing from your target quantity and a shipping date.