WIT 50-100K-HU-AU
50 – 100 kWThree-phaseIP66
View details
WIT 50-150K-XHU-US
Hybrid inverter · Three-phase · 50 – 150 kW
50 – 150 kWThree-phaseIP66
Price on request
50 – 150 kWRated power
Three-phasePhase
10MPPT trackers
98.5 %Max. efficiency
Technical data
| WIT 50K-XHU-US | WIT 63K-XHU-US | WIT 75K-XHU-US | WIT 85K-XHU-US | WIT 100K-XHU-US | WIT 125K-XHU-US | WIT 150K-XHU-US | |
|---|---|---|---|---|---|---|---|
| PV input | |||||||
| Max. PV input power (W) | 100000 | 126000 | 150000 | 170000 | 200000 | 250000 | 250000 |
| Max. PV input voltage (V) | 1000 | ||||||
| MPPT voltage range (V) | 180 – 1000 | ||||||
| Start-up voltage (V) | 195 | ||||||
| Max. input current per MPPT (A) | 42 | ||||||
| Max. short-circuit current per MPPT (A) | 50 | ||||||
| Number of MPPT trackers | 10 | ||||||
| PV strings per MPPT | 2 | ||||||
| AC output | |||||||
| Rated output power (W) | 50000 | 63000 | 75000 | 85000 | 100000 | 125000 | 150000 |
| Max. apparent power (VA) | 55000 | 69300 | 82500 | 93500 | 110000 | 137500 | 165000 |
| Rated AC voltage (V) | 480 | ||||||
| Phase | Three-phase | ||||||
| Rated AC frequency (Hz) | 50/60 | ||||||
| Max. AC output current (A) | 66.2 | 83.4 | 99.3 | 112.5 | 132.4 | 165.5 | 198.6 |
| Power factor | -1 to +1 (adjustable) | ||||||
| Total harmonic distortion (THDi) (%) | <3 | ||||||
| Backup output power (W) | 50000 | 63000 | 75000 | 85000 | 100000 | 125000 | 150000 |
| Peak (surge) power (W) | 80000 | 100800 | 120000 | 136000 | 160000 | 200000 | 240000 |
| Generator input | Yes | ||||||
| Max. parallel units | 10 | ||||||
| Nominal AC voltage and range (grid) | 277/480 V, -15% to +10% | ||||||
| AC grid connection type | 3P3W+PE / 3P4W+PE | ||||||
| Nominal AC grid frequency range (50 Hz / 60 Hz) (Hz) | 45-55 / 55-65 | ||||||
| AC/GEN input: Rated input power (W) | 50000 | 63000 | 75000 | 85000 | 100000 | 125000 | 150000 |
| AC/GEN input: Max. input current (A) | 250 | ||||||
| Backup: Max. AC apparent power (VA) | 55000 | 69300 | 82500 | 93500 | 110000 | 137500 | 165000 |
| Backup: Nominal AC voltage | 277 V (L-N); 480 V (L-L) | ||||||
| Backup: Nominal AC output frequency (Hz) | 50/60 | ||||||
| Backup: Load connection | 3P3W+PE / 3P4W+PE | ||||||
| Backup: Max. output current (A) | 66.2 | 83.4 | 99.3 | 112.5 | 132.4 | 165.5 | 198.6 |
| Backup: THDv (linear load) (%) | <3 | ||||||
| Backup: Load unbalance | 100% three-phase unbalanced | ||||||
| Backup: Overload capability | <=110%: continuous; 160%: 10 s | ||||||
| Backup: On/off-grid transfer time | <=10 ms | ||||||
| Battery | |||||||
| Battery voltage range (V) | 180 – 1000 | ||||||
| Max. charge current (A) | 200 | ||||||
| Max. discharge current (A) | 200 | ||||||
| Max. charge power (W) | 50000 | 63000 | 75000 | 85000 | 100000 | 125000 | 150000 |
| Max. discharge power (W) | 50000 | 63000 | 75000 | 85000 | 100000 | 125000 | 150000 |
| Battery voltage derating | Derating above 900 V | ||||||
| BMS communication | RS485 / CAN | ||||||
| Efficiency | |||||||
| Max. efficiency (%) | 98.5 | ||||||
| Protection | |||||||
| Protection functions | DC reverse polarity protection; Battery reverse protection; AC/DC surge protection (Type II); Insulation resistance monitoring; Ground fault monitoring; Grid monitoring; Residual-current monitoring unit; AC short-circuit protection; Strings monitoring; Anti-islanding protection; PID protection; AFCI function | ||||||
| General data | |||||||
| Dimensions (W x H x D) (mm) | 720 × 1360 × 400 | ||||||
| Weight (kg) | 160 | ||||||
| Ingress protection (IP rating) | IP66 | ||||||
| Operating temperature range (°C) | −30 – 60 | ||||||
| Relative humidity (%) | 0 – 100 | ||||||
| Max. operating altitude (m) | 4000 | ||||||
| Cooling | Smart air cooling | ||||||
| Topology | Transformerless | ||||||
| Warranty (years) | 5 – 10 | ||||||
| Max. DC/AC ratio | 2.0 | ||||||
| UPS function (built-in) | Yes | ||||||
| Black start function | Yes | ||||||
| Smart load function | Yes | ||||||
| Communication | |||||||
| Display | OLED + LED; Wi-Fi + app | ||||||
| Communication interfaces | RS485; CAN; Wi-Fi (optional); 4G (optional); LAN (optional) | ||||||
| Certifications | |||||||
| Certifications and standards | UL 1741:2021; UL 1741 Mutimod; CSA 22.2 No. 107; UL 1998; UL 1699B; UL 3141; E 5000; FCC Part 15 | ||||||
| Grid codes | IEEE 1547:2018; IEEE 1547.1:2020; HECO Rule 14; UL 1741 SA/SB:2020; CSA 22.3 No.9; CEC/SGIP | ||||||
Values from the manufacturer's datasheet, pending final confirmation. The datasheet supplied with the product prevails.
Downloads
Applications
Works with
WIT 50-100K-HU-AU
50 – 100 kWThree-phaseIP66
View details
SUN-60-80K-SG02HP3-EU-EM6
60 – 80 kWThree-phaseIP65
View details
WIT 63-125K-XHU
63 – 125 kWThree-phaseIP66
View details
Request a quotation
You receive the datasheet, certificates, tiered pricing from your target quantity and a shipping date.