WIT 50-100K-HU-AU Hybrid inverter

WIT 50-100K-HU-AU

Hybrid inverter · Three-phase · 50 – 100 kW

50 – 100 kWThree-phaseIP66
Price on request
50 – 100 kWRated power
Three-phasePhase
7 – 10MPPT trackers
98.2 %Max. efficiency

Technical data

WIT 50K-HUWIT 63K-HUWIT 75K-HUWIT 100K-HU
PV input
Max. PV input power (W)109200124800156000156000
Max. PV input voltage (V)1000
Rated PV input voltage (V)550
MPPT voltage range (V)180 – 800
Start-up voltage (V)195
Max. input current per MPPT (A)32
Max. short-circuit current per MPPT (A)40
Number of MPPT trackers781010
PV strings per MPPT2
AC output
Rated output power (W)500006300075000100000
Max. apparent power (VA)550006930082500110000
Rated AC voltage (V)400
PhaseThree-phase
Rated AC frequency (Hz)50/60
Max. AC output current (A)83.3105125166.7
Power factor-1 to +1 (adjustable)
Total harmonic distortion (THDi) (%)<3
Backup output power (W)500006300075000100000
Nominal AC voltage and range (grid)380/400/415 V, -15% to +10%
AC grid connection type3P3W+PE / 3P4W+PE
Nominal AC grid frequency range (50 Hz / 60 Hz) (Hz)45-55 / 55-65
AC input data (grid): Nominal power (kW)50 / 10063 / 12675 / 150100 / 200
AC input data (grid): Max. apparent power (kVA)55 / 10069.3 / 12682.5 / 150110 / 200
AC input data (grid): Max. current (A)83.3 / 151.5105 / 190.9125 / 227.3166.7 / 303
Backup: Max. AC apparent power (VA)600007560090000120000
Backup: Rated AC output voltage220/230/240 V (L-N); 380/400/415 V (L-L)
Backup: Nominal AC output frequency (Hz)50/60
Backup: Load connection3P3W+PE / 3P4W+PE
Backup: Max. output current (A)90.9114.5136.4181.8
Backup: THDv (linear load) (%)<3
Backup: Load unbalance100% three-phase unbalanced
Backup: Overload capability<=110%: continuous; 110-120%: <10 min; >120%: 200 ms
Backup: On/off-grid transfer time<=10 ms
Battery
Battery voltage range (V)600 – 1000
Max. charge current (A)83.3105125167
Max. discharge current (A)83.3105125167
Max. charge power (W)567007140085100113500
Max. discharge power (W)567007140085100113500
Battery voltage range by grid connection600-1000 V (3P3W); 680-1000 V (3P4W); derating above 850 V
Recommended battery voltage (V)768
BMS communicationRS485 / CAN
Efficiency
Max. efficiency (%)98.2
European efficiency (%)97.8
Protection
Protection functionsPV reverse polarity protection; Battery reverse protection; AC/DC surge protection (Type II); Insulation resistance monitoring; Ground fault monitoring; Grid monitoring; Residual-current monitoring unit; AC short-circuit protection; Strings monitoring; Anti-islanding protection; PID protection; AFCI function (optional)
General data
Dimensions (W x H x D) (mm)820 × 1350 × 510
Weight (kg)153153160160
Ingress protection (IP rating)IP66
Operating temperature range (°C)−30 – 60
Relative humidity (%)0 – 100
Max. operating altitude (m)4000
CoolingSmart air cooling
TopologyTransformerless
Warranty (years)5 – 10
UPS functionYes
Black start functionYes
Diesel generator (DG) remote controlYes
Grid-support functionsYes
Max. system capacity (scalable configuration) (kW)300
Communication
DisplayOLED + LED; Wi-Fi + app
Communication interfacesRS485; CAN; USB; Wi-Fi (optional); LAN (optional)
Certifications
Certifications and standardsEN 62920:2017; IEC/EN 62477-1; IEC/EN 62109-1; IEC/EN 62109-2
Grid codesIEC 62116; IEC 61727; G99:2020; EN 50549-1; VDE 4105; NRS 097-2-1

Values from the manufacturer's datasheet, pending final confirmation. The datasheet supplied with the product prevails.

Downloads

Datasheets

Applications

Works with

Request a quotation

You receive the datasheet, certificates, tiered pricing from your target quantity and a shipping date.

Fields marked * are required.

One working day reply. Your details are used for this quote only. How we handle your data: Privacy

Price on request Get a quote