WIT+AXE System
50 kWh29.9 – 50 kW512 V
View details
RISE 261H-XH
C&I storage system · 261 kWh
261 kWh50 – 125 kW832 V
Price on request
261 kWhEnergy capacity
832 VNominal voltage
50 – 125 kWRated power
IP55Protection class
Technical data
| RISE 261H-5H | RISE 261H-4H | RISE 261H-3H | RISE 261H-2H | |
|---|---|---|---|---|
| PV input | ||||
| Max. PV input power (W) | 100000 | 126000 | 170000 | 250000 |
| Start-up voltage (V) | 195 | |||
| Max. PV input voltage (V) | 1100 | |||
| Max. open-circuit voltage of PV (V) | 1000 | |||
| MPPT voltage range (V) | 180 – 1000 | |||
| Max. input current per MPPT (A) | 42 | |||
| Max. short-circuit current per MPPT (A) | 50 | |||
| PV strings per MPPT | 2 | |||
| Number of MPPT trackers | 10 | |||
| DC/AC ratio | 2.0 | |||
| AC output | ||||
| Rated output power (W) | 50000 | 63000 | 85000 | 125000 |
| Max. apparent power (VA) | 55000 | 69300 | 93500 | 137500 |
| Rated AC voltage (V) | 400 | |||
| Phase | Three-phase | |||
| Rated AC frequency (Hz) | 50/60 | |||
| Max. AC output current (A) | 83.3 | 105 | 141.7 | 208.3 |
| Power factor | -1 to +1 (adjustable) | |||
| Total harmonic distortion (THDi) (%) | <3 | |||
| Backup output power (W) | 50000 | 63000 | 85000 | 125000 |
| Peak (surge) power (W) | 80000 | 100800 | 136000 | 200000 |
| Generator input | Yes | |||
| Nominal AC voltage options and range | 380/400 V, -15% to +10% | |||
| Nominal AC grid frequency range (Hz) | 45-55 / 55-65 | |||
| AC grid connection type | 3P4W+PE | |||
| Rated AC input power (grid) (kW) | 50 | 63 | 85 | 125 |
| Max. AC input current (A) | 250 | |||
| Max. AC apparent power (off-grid) (kVA) | 55 | 69.3 | 93.5 | 137.5 |
| Rated AC output voltage (off-grid) | 220/230 V (L-N); 380/400 V (L-L) | |||
| Nominal AC output frequency (off-grid) (Hz) | 50/60 | |||
| Load connection type (off-grid) | 3P4W+PE | |||
| Max. output current (off-grid) (A) | 83.3 | 105 | 141.7 | 208.3 |
| THDv (off-grid, linear load) (%) | <3 | |||
| Load unbalance (off-grid) | 100% three-phase unbalanced | |||
| Overload capacity (off-grid) | <=110%: continuous; 160%: 10 s | |||
| On/off-grid transfer time (ms) | ≤10 | |||
| GEN port rated voltage (V) | 380/400 | |||
| GEN port rated frequency (Hz) | 50/60 | |||
| GEN port connection type | 3P4W+PE | |||
| GEN port rated input power (GEN / AC coupling) (kW) | 50 | 63 | 85 | 125 |
| GEN port rated input power (smart load) (kW) | 50 | 63 | 85 | 125 |
| Battery | ||||
| Cell type | LFP (3.2 V / 314 Ah) | |||
| Nominal voltage (V) | 832 | |||
| Operating voltage range (V) | 728 – 936 | |||
| Depth of discharge (DoD) (%) | 95 | |||
| Max. expandable energy (Wh) | 2610000 | |||
| Battery module energy (kWh) | 52.24 | |||
| Battery module configuration | 1P52S | |||
| Battery system configuration | 1P260S | |||
| Charge/discharge rate | <=0.5P | |||
| Max. cell temperature difference (°C) | ≤2.5 | |||
| General data | ||||
| Dimensions (W x H x D) (mm) | 1400 × 2150 × 1300 | |||
| Weight (kg) | 2600 | |||
| Ingress protection (IP rating) | IP55 | |||
| Operating temperature range (°C) | −25 – 55 | |||
| Relative humidity (%) | 0 – 95 | |||
| Max. operating altitude (m) | 3000 | |||
| Cooling | Smart air cooling for PCS; liquid cooling for battery | |||
| Warranty (years) | 5 – 10 | |||
| Communication | ||||
| Communication interfaces | RS485; USB | |||
| Certifications | ||||
| Certifications and standards | CE/CB; RoHS; IEC 62109-1/2; IEC 61683; IEC 60068; UN 38.3; IEC 62619; IEC 62477-1; IEC 62933; REACH; UL 9540A | |||
| Grid codes | IEC 62116; IEC 61727; EN 50549-1-10; EN 50549-2-10; CEI 0-16; CEI 0-21; UNE 21700/NTS; NRS 097-2-1 | |||
| System | ||||
| System energy capacity (kWh) | 261 | |||
| Fire protection | Aerosol (multi-level fire protection) | |||
| Max. scalable system power (kW) | 1250 | |||
Values from the manufacturer's datasheet, pending final confirmation. The datasheet supplied with the product prevails.
Downloads
Applications
Works with
WIT+AXE System
50 kWh29.9 – 50 kW512 V
View details
100kW-2.5MW C&I ESS (AC-DC)
257.23 kWh100 – 125 kW819.2 V
View details
100kW-2.5MW C&I ESS (STS)
257.23 kWh100 – 125 kW819.2 V
View details
Request a quotation
You receive the datasheet, certificates, tiered pricing from your target quantity and a shipping date.