100kW-2.5MW C&I ESS (AC-DC)
257.23 kWh100 – 125 kW819.2 V
View details
WIT+AXE System
C&I storage system · 50 kWh
50 kWh29.9 – 50 kW512 V
Price on request
50 kWhEnergy capacity
512 VNominal voltage
29.9 – 50 kWRated power
IP66Protection class
Technical data
| WIT 29.9K-XHU | WIT 30K-XHU | WIT 36K-XHU | WIT 40K-XHU | WIT 50K-XHU | |
|---|---|---|---|---|---|
| PV input | |||||
| Max. PV input power (W) | 59800 | 60000 | 72000 | 80000 | 100000 |
| Start-up voltage (V) | 195 | ||||
| Max. PV input voltage (V) | 1100 | ||||
| Rated PV input voltage (V) | 620 | ||||
| MPPT voltage range (V) | 180 – 1000 | ||||
| Full-load DC voltage range (V) | 375 – 850 | 375 – 850 | 450 – 850 | 500 – 850 | 620 – 850 |
| Max. input current per MPPT (A) | 40 | ||||
| Max. short-circuit current per MPPT (A) | 50 | ||||
| PV strings per MPPT | 2 | ||||
| Number of MPPT trackers | 4 | ||||
| AC output | |||||
| Rated output power (W) | 29900 | 30000 | 36000 | 40000 | 50000 |
| Max. apparent power (VA) | 29900 | 33000 | 39600 | 44000 | 55000 |
| Rated AC voltage (V) | 400 | ||||
| Phase | Three-phase | ||||
| Rated AC frequency (Hz) | 50/60 | ||||
| Max. AC output current (A) | 45.3 | 50 | 60 | 66.7 | 83.3 |
| Power factor | >0.99 (at nominal power); adjustable -1 to +1 | ||||
| Total harmonic distortion (THDi) (%) | <3 | ||||
| Backup output power (W) | 29900 | 30000 | 36000 | 40000 | 50000 |
| Peak (surge) power (W) | 44850 | 45000 | 54000 | 60000 | 75000 |
| Max. parallel units | 10 | ||||
| Nominal AC voltage options and range | 380/400 V, -15% to +10% | ||||
| AC grid connection type | 3P3W+PE / 3P4W+PE | ||||
| Nominal AC grid frequency range (Hz) | 45-55 / 55-65 | ||||
| Max. input current (GEN / AC coupling) (A) | 90.6 / 45.3 | 100 / 45.5 | 120 / 54.5 | 133.3 / 60.7 | 166.7 / 75.7 |
| Max. output current (smart load) (A) | 200 | ||||
| Backup: Max. AC apparent power (kVA) | 29.9 | 45 | 54 | 60 | 75 |
| Backup: Nominal AC voltage | 220/230 V (L-N); 380/400 V (L-L) | ||||
| Backup: Nominal AC frequency (Hz) | 50/60 | ||||
| Backup: Max. output current (A) | 68.0 | 68.2 | 81.8 | 91 | 113.6 |
| Backup: Overload capability | 1.5 x rated power, 10 s | ||||
| Backup: THDv (linear full load) (%) | <3 | ||||
| Battery | |||||
| Battery voltage range (V) | 200 – 900 | ||||
| Number of battery inputs | 3 | ||||
| Max. charging / discharging current per battery input (A) | 55 | ||||
| BMS communication | RS485; CAN | ||||
| Battery system models | AXE 50.0H-1HT-S1 / AXE 60.0H-1HT-S1 | ||||
| Battery type | Lithium-ion | ||||
| System energy capacity (kWh) | 50 – 60 | ||||
| Usable energy capacity (Wh) | 45000 – 54000 | ||||
| Nominal voltage (V) | 512 – 614.4 | ||||
| Battery system operating voltage range (AXE 50.0H / AXE 60.0H) (V) | 464-568 / 556.8-681.6 | ||||
| Battery system: Max. charge/discharge current (A) | 100 | ||||
| Max. discharge power (W) | 50000 – 60000 | ||||
| Max. expandable energy (Wh) | 180000 | ||||
| Battery modules in series (AXE 50.0H / AXE 60.0H) | 10 / 12 | ||||
| Battery module model | AXE 5.0H-E1 EU | ||||
| Battery module nominal energy (kWh) | 5 | ||||
| Battery module nominal voltage (V) | 51.2 | ||||
| Battery module operating voltage range (V) | 46.4 – 56.8 | ||||
| Battery module dimensions (W x H x D) (mm) | 482 × 131 × 580 | ||||
| Battery module weight (kg) | ≤47 | ||||
| Efficiency | |||||
| Max. efficiency (%) | 98.1 | ||||
| Protection | |||||
| Protection functions | DC reverse polarity protection; Battery reverse protection; Insulation resistance monitoring; AC/DC surge protection (Type II); AC short-circuit protection; Ground fault monitoring; Grid monitoring; String monitoring; Anti-islanding protection; Residual-current monitoring unit | ||||
| General data | |||||
| Dimensions (W x H x D) (mm) | 920 × 585 × 320 | ||||
| Weight (kg) | 92 | ||||
| Ingress protection (IP rating) | IP66 | ||||
| Operating temperature range (°C) | −30 – 60 | ||||
| Relative humidity (%) | 0 – 95 | ||||
| Max. operating altitude (m) | 4000 | ||||
| Cooling | Smart air cooling | ||||
| Noise level (dB) | ≤55 | ||||
| Topology | Transformerless | ||||
| Warranty (years) | 5 – 10 | ||||
| Battery system: Installation style | Floor stand | ||||
| Battery system: Dimensions (W x H x D) (mm) | 800 × 2000 × 1000 | ||||
| Battery system: Weight (AXE 50.0H / AXE 60.0H) (kg) | <=900 / <=1000 | ||||
| Battery system: Ingress protection | IP55 | ||||
| Battery system: Operating temperature (°C) | −25 – 55 | ||||
| Battery system: Relative humidity (%) | 5 – 95 | ||||
| Battery system: Cooling | Air cooling | ||||
| Battery system: Noise (dB) | <65 | ||||
| Battery system: Max. altitude (m) | 2000 | ||||
| Battery system: Warranty (years) | 10 | ||||
| Communication | |||||
| Display | OLED + LED; APP | ||||
| Communication interfaces | RS485; USB; CAN; Wi-Fi (optional); LAN (optional) | ||||
| Control module communication port | CAN; RS485; USB | ||||
| Monitoring parameters | SOC, system voltage, current, cell voltage, cell temperature, PCBA temperature | ||||
| Certifications | |||||
| Certifications and standards | IEC/EN 61000-6-1; IEC/EN 61000-6-3; IEC/EN 62109-1; IEC/EN 62109-2; UN 38.3; IEC 62619; IEC 60730; IEC 62477; CE; RoHS; UKCA | ||||
| Grid codes | NRS 097-2-1:2017; EN 50549-1; IEC 62116; IEC 61727; G99:2020; VDE 4105 | ||||
| System | |||||
| Compatible battery system options per inverter | AXE 50.0H-1HT-S1 x1 (51.2 kWh); AXE 55.0H-1HT-S1 x1 (56.32 kWh); AXE 60.0H-1HT-S1 x1 (61.44 kWh); AXE 50.0-60.0H-1HT-S1 x2 (61.44-122.88 kWh); AXE 50.0-60.0H-1HT-S1 x3 (92.16-184.32 kWh) | ||||
| Control module model | AXE 1000100-C1 | ||||
| Number of control modules | 1 | ||||
| Control module dimensions (W x H x D) (mm) | 482 × 131 × 580 | ||||
| Control module weight (kg) | ≤15 | ||||
| Control module operating voltage range (V) | 120 – 1000 | ||||
| Control module max. current (A) | 100 | ||||
Values from the manufacturer's datasheet, pending final confirmation. The datasheet supplied with the product prevails.
Downloads
Applications
Works with
100kW-2.5MW C&I ESS (AC-DC)
257.23 kWh100 – 125 kW819.2 V
View details
100kW-2.5MW C&I ESS (STS)
257.23 kWh100 – 125 kW819.2 V
View details
RISE 261H-XH
261 kWh50 – 125 kW832 V
View details
Request a quotation
You receive the datasheet, certificates, tiered pricing from your target quantity and a shipping date.